A feeder is protected by a 100 A overcurrent device. Using Table 250.122, the minimum size copper equipment grounding conductor is:
a.12 AWG
b.10 AWG
c.8 AWG
d.6 AWG
Giải thích
Table 250.122 lists an 8 AWG copper equipment grounding conductor for circuits protected at 100 A. A 10 AWG is the value for 60 A, and 6 AWG is for larger ratings up to 200 A, so both miss the 100 A row.
Trích dẫn luật: 2023 NEC §250.122Luyện miễn phí toàn bộ 521 câu hỏi — không cần đăng ký.