A single made rod electrode is measured at 40 ohms resistance to earth. The code requires that it be:
a.Left as is because 40 ohms is acceptable
b.Replaced with a copper water pipe
c.Bonded to the neutral only
d.Augmented with one additional electrode (or otherwise meet 25 ohms)
Giải thích
Per 250.53(A)(2), a single rod, pipe, or plate electrode that does not have a resistance to earth of 25 ohms or less must be supplemented by one additional electrode. Because 40 ohms exceeds 25 ohms, a second electrode is required; leaving it or bonding only to the neutral does not comply.
Trích dẫn luật: 2023 NEC §250.53Luyện miễn phí toàn bộ 521 câu hỏi — không cần đăng ký.