Service-entrance conductors are 3/0 AWG copper. Per Table 250.102(C)(1), what is the minimum copper main bonding jumper?
a.6 AWG
b.4 AWG
c.2 AWG
d.8 AWG
Giải thích
The main bonding jumper is sized from Table 250.102(C)(1) based on the service conductors; for 2/0-3/0 copper it is 4 AWG copper. 6 AWG and 8 AWG are too small, and 2 AWG is not required until conductors exceed 3/0.
Trích dẫn luật: 2023 NEC §250.28Luyện miễn phí toàn bộ 521 câu hỏi — không cần đăng ký.