InstallationCâu 26 / 110
A high-efficiency condensing furnace (Category IV) is typically vented with what material?
a.Type B double-wall metal vent
b.Single-wall galvanized pipe
c.Listed PVC or CPVC plastic pipe
d.Masonry chimney only
Giải thích
Condensing furnaces cool flue gases below their dew point, producing acidic condensate and low-temperature exhaust, so they are vented with listed plastic pipe such as PVC or CPVC. Metal Type B vent would corrode and is not rated for positive-pressure condensing appliances. Manufacturer instructions specify approved materials and lengths.
Trích dẫn luật: 2022 California Mechanical Code (CMC)Luyện miễn phí toàn bộ 110 câu hỏi — không cần đăng ký.