Drainage, Waste and Vent (DWV)

The DWV system carries waste away by gravity while venting keeps air pressure balanced so trap seals are not lost. This chapter covers drain sizing by fixture units, slope, traps and trap seals, venting, cleanouts, and interceptors.

Drain Sizing by Drainage Fixture Units

Drain, waste, and vent piping is sized using drainage fixture units (DFU), a value that represents the discharge load of each fixture. The DFU loads are totaled and matched to a code table that gives the required pipe size for a given slope.

Drainage fixture unit (DFU)
A value representing the probable discharge of a fixture into the drainage system, used to size drains and sewers.
2022 California Plumbing Code (CPC) §702.0
Total the load
Add the DFU of all fixtures on a drain, then select the pipe size from the code table for the chosen slope.
Never reduce downstream
The size of a drainage pipe must not decrease in the direction of flow toward the sewer.
Building drain and sewer
The building drain and building sewer are sized for the total connected DFU using the drainage sizing tables.
2022 California Plumbing Code (CPC) §703.0

Slope and Grade

Horizontal drainage piping must slope so that solids are carried along by the flow; too little slope lets solids settle and too much can let liquid outrun solids. California sets one minimum slope for every size of horizontal drain, and lets larger pipe run flatter only as a conditional exception.

Minimum slope
Horizontal drainage piping shall be run in practical alignment and at a uniform slope of not less than 1/4 inch per foot, or 2 percent, toward the point of disposal — at every pipe size, not just small pipe.
2022 California Plumbing Code (CPC) §708.1
Reduced slope for large pipe
Only where 1/4 inch per foot is impractical because of the depth of the street sewer, the structural features, or the arrangement of the building may pipe 4 inches or larger be sloped at not less than 1/8 inch per foot, or 1 percent, and then only where first approved by the Authority Having Jurisdiction.
2022 California Plumbing Code (CPC) §708.1
Uniform grade
Grade should be uniform and continuous so there are no low spots that trap waste or create bellies in the line.
Flow velocity
Slope is chosen to keep a self-scouring velocity that carries solids without leaving the liquid behind.

Traps and Trap Seals

A trap holds a water seal that blocks sewer gases from entering the building through a fixture. The seal depth and the distance from the trap to its vent are regulated so the seal is not siphoned or blown out.

Trap seal depth
Each fixture trap shall have a liquid seal of not less than 2 inches and not more than 4 inches, except where the Authority Having Jurisdiction finds a deeper seal necessary.
2022 California Plumbing Code (CPC) §1005.1
One trap per fixture
Each fixture is separately trapped, and a fixture must not be double trapped because a second trap can lock the flow.
Prohibited traps
S-traps, bell traps, and traps with moving parts are prohibited because they can lose their seal or clog.
Trap arm
The trap arm is the drain between the trap weir and the vent. It may change direction up to 90 degrees without a cleanout — up to 135 degrees where the trap arm is 3 inches or larger — and for a water closet or similar fixture the developed length from the top of the closet flange to the inner edge of the vent shall not exceed 6 feet.
2022 California Plumbing Code (CPC) §1002.3 and Table 1002.2, Note 2

Trap-to-Vent Distance and Venting

Every trap must be vented so that discharge does not siphon the seal. The maximum distance from the trap to its vent depends on the size of the trap arm, and several venting methods can satisfy the requirement.

Maximum trap-to-vent distance
The developed length of the trap arm from the trap weir to the inner edge of the vent shall be not less than two times the diameter of the trap arm and not more than Table 1002.2 allows: 30 inches for a 1-1/4 inch trap arm, 42 inches for 1-1/2 inch, 60 inches for 2 inch, 72 inches for 3 inch, and 120 inches for 4 inch and larger, with 1/4 inch per foot of slope maintained.
2022 California Plumbing Code (CPC) §1002.2 and Table 1002.2
Individual vent
A vent that serves a single fixture trap and connects to the vent system or extends to open air.
Common vent
A single vent that serves two fixture traps connected at the same level, permitted within code limits.
Wet vent
A pipe that serves as both a drain for one fixture and a vent for another, allowed under specific code conditions.
Vent termination
A vent must extend through its flashing and terminate not less than 6 inches above the roof and not less than 1 foot from a vertical surface, and not less than 10 feet from — or not less than 3 feet above — an openable window, door, opening, air intake, or vent shaft. Where the roof is used for assembly or parking, a vent within 10 feet of that area must extend not less than 7 feet above it.
2022 California Plumbing Code (CPC) §906.1, §906.2 and §906.3

Cleanouts and Interceptors

Cleanouts give access to clear stoppages in the drainage system, and interceptors separate harmful or clogging substances such as grease, oil, or sand before they reach the sewer. Both are placed where the code and the hazard require.

Cleanout access
A cleanout in piping 2 inches or less must have not less than 18 inches by 18 inches of clearance in front of it, and one in piping exceeding 2 inches not less than 24 inches by 24 inches. An under-floor cleanout may be no more than 5 feet from an access door, trap door, or crawl hole, with not less than 30 inches of horizontal clearance from the means of access.
2022 California Plumbing Code (CPC) §707.9
Cleanout spacing
Each horizontal drainage pipe needs a cleanout at its upper terminal, and a run more than 100 feet in total developed length needs a cleanout for each 100 feet or fraction thereof. An additional cleanout is required for each aggregate horizontal change in direction exceeding 135 degrees.
2022 California Plumbing Code (CPC) §707.4
Grease interceptor
Kitchens and food service that discharge grease must install an approved grease interceptor to keep grease out of the sewer.
2022 California Plumbing Code (CPC) §1014.0
Sand and oil interceptors
Garages and industrial drains use sand or oil interceptors to catch heavy solids and petroleum before they enter the drainage system.