Thoát nước, Nước thải & Thông hơiCâu 120 / 360
A horizontal branch serves two water closets (3 DFU each), two lavatories (1 DFU each), and two showers (2 DFU each). What is the minimum branch size?
a.2 inch
b.4 inch
c.1-1/2 inch
d.3 inch
Giải thích
The load is (2 x 3) + (2 x 1) + (2 x 2) = 6 + 2 + 4 = 12 DFU. A 3 inch branch carries up to 20 DFU and allows a maximum of two water closets, so it fits both the 12 DFU load and the two closets. A 2 inch branch (6 DFU) and 1-1/2 inch branch (3 DFU) are undersized, and a 4 inch branch is larger than needed here.
Trích dẫn luật: 2022 California Plumbing Code (CPC) §703.0 (Table 703.1)Luyện miễn phí toàn bộ 360 câu hỏi — không cần đăng ký.