A double check valve assembly (DC) is being selected for a cross-connection. Which application is appropriate for a DC assembly?
a.A high (health) hazard with chemical contamination
b.A low-hazard (non-health) cross-connection, including backpressure situations
c.Any hazard as long as an air gap is impossible
d.A back-siphonage-only application where an AVB is cheaper
Giải thích
A double check assembly protects against both back-siphonage and backpressure but only for low-hazard (non-health) cross-connections. It is not rated for a high (health) hazard, which requires an RP assembly or air gap, so the other options misapply the device.
Trích dẫn luật: 2022 California Plumbing Code (CPC) §603.0Luyện miễn phí toàn bộ 360 câu hỏi — không cần đăng ký.
Câu hỏi liên quan cùng chủ đề
- A lawn sprinkler system has no chemical injection and no possibility of backpressure, only back-siphonage under continuous pressure. Which device is the appropriate minimum protection?
- A residence has a closed water supply system because the water meter contains a check valve and a pressure regulator. As the water heater heats water, pressure spikes dangerously. What does the code require to relieve this?
- Which of the following is an approved standard material for potable cold and hot water distribution piping inside a building?
- A branch serves fixtures totaling 8 WSFU. Design velocity should be kept at or below about 8 feet per second to limit erosion and noise. If a given pipe size carries the demand at 6 fps, and the next size down would run at 11 fps, which is the better selection and why?
- What is the fundamental purpose of cross-connection control in a potable water system?
- When sizing water piping using the fixture unit method, why is the total demand in gpm always less than the simple sum of every fixture's peak flow?
Cập nhật gần nhất: · quy trình kiểm tra
Đội Ngũ Biên Tập PrepPass · Đối chiếu với California CSLB C-36 Plumbing Trade Examination · Quy trình kiểm tra