Thoát nước, Nước thải & Thông hơiCâu 148 / 360
For a 2-inch trap arm, the maximum developed length from the trap weir to the vent (per the CPC trap-to-vent table) is approximately…
a.2 feet
b.3 feet 6 inches
c.3 feet
d.5 feet (for 2-inch pipe)
Giải thích
The maximum trap-to-vent distance grows with pipe size: about 2 ft 6 in for 1-1/4 inch, 3 ft 6 in for 1-1/2 inch, and 5 feet for 2-inch pipe. Exceeding the distance risks self-siphoning the trap because the vent is too far to relieve pressure. The trap arm must also maintain proper slope within this length.
Luyện miễn phí toàn bộ 360 câu hỏi — không cần đăng ký.