Cấp nước & Phân phốiCâu 36 / 360
A pressure-reducing valve is set to deliver 65 psi downstream from a 110 psi street pressure. On a closed system, what additional device is commonly required to accompany the PRV?
a.A second meter
b.A larger service
c.A gate valve only
d.Thermal expansion control (expansion tank), because the check in the PRV closes the system
Giải thích
Because a PRV typically includes or creates a check that closes the system, thermal expansion control such as an expansion tank is commonly required to absorb pressure rise from water heating. A second meter, larger service, or a gate valve alone would not relieve thermal expansion in the closed system.
Trích dẫn luật: 2022 California Plumbing Code (CPC) §608.2Luyện miễn phí toàn bộ 360 câu hỏi — không cần đăng ký.
Câu hỏi liên quan cùng chủ đề
- A commercial building connects to a boiler that uses chemical additives and is served from the potable main. What premise-isolation protection does the code generally require at the service?
- A fixture requires a minimum flow (residual) pressure of 8 psi to operate correctly. During peak demand your calculation shows only 5 psi available at that fixture. What is the correct interpretation?
- Which characteristic makes CPVC acceptable for hot water distribution where standard PVC is not?
- What is the essential difference between back-siphonage and backpressure backflow?
- A meter and service are being sized. The peak demand is 24 gpm at a required 20 psi residual. Available static street pressure is 55 psi, and the total pressure loss budget (meter, elevation, friction, fittings) is calculated at 40 psi. Is the design feasible?
- Which joining method is appropriate for Type L copper water tube?
Cập nhật gần nhất: · quy trình kiểm tra
Đội Ngũ Biên Tập PrepPass · Đối chiếu với California CSLB C-36 Plumbing Trade Examination · Quy trình kiểm tra