Cấp nước & Phân phốiCâu 43 / 360
A dedicated fire sprinkler system without antifreeze or chemical additives is connected to the potable main. Which backflow protection is generally the minimum appropriate for this typically low-hazard connection?
a.No protection
b.An atmospheric vacuum breaker
c.A double check valve assembly (DC)
d.A hose bibb vacuum breaker
Giải thích
A fire system without chemicals or antifreeze is typically a low hazard, and the standing water in the system justifies at least a double check valve assembly for premise isolation. No protection is unacceptable, an AVB cannot be under continuous pressure, and a hose bibb vacuum breaker is not a system-isolation assembly.
Trích dẫn luật: 2022 California Plumbing Code (CPC) §603.0Luyện miễn phí toàn bộ 360 câu hỏi — không cần đăng ký.
Câu hỏi liên quan cùng chủ đề
- A mechanical water hammer arrestor uses a sealed piston or bellows with a gas charge. Why is this preferred over an old-style capped air chamber?
- An unprotected submerged inlet exists where a hose lies in a mop bucket filled with dirty water, connected to a faucet under pressure. What type of hazard does this arrangement represent?
- When calculating developed length for water pipe sizing, what does developed length include?
- Two identical branches serve the same fixture group, but branch A is 20 feet long and branch B is 80 feet long, same diameter and flow. Which statement about friction loss is correct?
- A testable backflow assembly such as an RP or DC must be installed so it can be maintained. Which installation requirement supports this?
- Elevation loss: a fixture is located 40 feet above the water meter. Using 0.433 psi per foot of elevation, how much static pressure is lost to elevation alone?