A technician uses recovery equipment manufactured after November 15, 1993 on an R-22 split system that normally holds less than 200 pounds of refrigerant. To what level must the appliance be evacuated during recovery?

a.0 inches Hg vacuum
b.10 inches Hg vacuum
c.15 inches Hg vacuum
d.4 inches Hg vacuum

Giải thích

R-22 is a high-pressure refrigerant (40 CFR §82.152 lists it by name). Under §82.156 Table 1, a high-pressure appliance with a full charge under 200 pounds must be evacuated to 0 inches Hg (atmospheric) with recovery equipment made on or after November 15, 1993. (b) 10 inches Hg is the level for a high-pressure appliance of 200 pounds or more, or for a medium-pressure appliance such as R-134a under 200 pounds; (c) 15 inches Hg is only for medium-pressure appliances of 200 pounds or more; (d) 4 inches Hg belongs to pre-1993 recovery equipment.

Trích dẫn luật: 40 CFR §82.156