Type II — High-PressureCâu 150 / 240
A technician replaces a leaking evaporator on an R-410A system and must protect the new POE oil during the repair. Why is POE oil handling important?
a.POE oil is flammable at room temperature and must be kept frozen
b.POE oil is highly hygroscopic and absorbs moisture from the air quickly, so the system should be kept sealed and evacuated well
c.POE oil never needs a vacuum because it repels water
d.POE oil can be mixed freely with mineral oil with no effect
Giải thích
Polyolester (POE) oil used with R-410A is very hygroscopic, meaning it absorbs moisture from the air rapidly, so the system should be left open as briefly as possible and evacuated to a deep vacuum. Excess moisture can cause acid formation and system damage. POE and mineral oil are not freely interchangeable, which matters during retrofits and repairs.
Luyện miễn phí toàn bộ 240 câu hỏi — không cần đăng ký.
Câu hỏi liên quan cùng chủ đề
- A technician recovers R-22 from a rooftop unit that holds 150 pounds using equipment made after November 15, 1993. To what vacuum must the system be evacuated during recovery?
- A technician is deciding between liquid and vapor recovery on a Type II system with a moderate charge. Which statement correctly compares the two?
- A technician is about to add liquid refrigerant into the suction line of a running compressor to charge faster. Why is this dangerous on a Type II system?
- Virgin (newly produced) HCFC-22 was subject to a production and import phaseout. As of January 1, 2020, what happened to the supply of virgin R-22?
- A technician measures subcooling of 3°F on a TXV-equipped R-410A system when the manufacturer specifies 10°F of subcooling. What does the low subcooling most likely indicate?
- Before opening a Type II system for a compressor change, a technician recovers the refrigerant. Which sequence best protects both the technician and the environment?