Regulations & SafetyCâu 44 / 240
A refrigerated warehouse uses a commercial refrigeration system with 300 pounds of refrigerant. What annual leak rate threshold applies to commercial refrigeration under the current rules?
a.10 percent
b.20 percent
c.30 percent
d.50 percent
Giải thích
Commercial refrigeration appliances have a leak rate threshold of 20 percent per year, higher than the 10 percent for comfort cooling but lower than the 30 percent for industrial process refrigeration. A 50 percent threshold does not exist under the rule. Once the calculated annual leak rate exceeds 20 percent, repairs must generally be completed within 30 days.
Trích dẫn luật: 40 CFR §82.157Luyện miễn phí toàn bộ 240 câu hỏi — không cần đăng ký.
Câu hỏi liên quan cùng chủ đề
- The detailed federal regulations that carry out Clean Air Act Section 608 are found in which part of the Code of Federal Regulations?
- A technician is caught knowingly venting refrigerant. Under the Clean Air Act, EPA may assess civil penalties of up to how much per day, per violation?
- Under the post-2019 leak repair rules, what is the annual leak rate threshold that triggers required repairs for a comfort-cooling appliance containing 50 or more pounds?
- An industrial process refrigeration system in a chemical plant contains 1,000 pounds of refrigerant. Which annual leak rate threshold applies?
- A technician stores refrigerant cylinders in a work van during summer. To avoid dangerous pressure buildup, cylinders should not be exposed to temperatures above:
- A technician is servicing a chiller in a small equipment room with poor ventilation. Which hazard is the greatest immediate concern if refrigerant leaks in that confined space?
Cập nhật gần nhất: · quy trình kiểm tra
Đội Ngũ Biên Tập PrepPass · Đối chiếu với EPA Section 608 Technician Certification Exam · Quy trình kiểm tra