Theory & SafetyCâu 118 / 120
Entrances at each end of the working space are generally required for equipment rated at least what value and over 6 feet wide?
a.1,000 amperes
b.800 amperes
c.1,200 amperes
d.600 amperes
Giải thích
Equipment rated 1,200 amperes or more and over 6 feet wide containing overcurrent, switching or control devices needs an entrance at each end of the working space so a worker is never trapped behind an arcing fault. The 1,000-ampere threshold belongs to service ground-fault protection, and 800 amperes is the ceiling for the next-standard-size overcurrent rule.
Trích dẫn luật: 2023 NEC §110.26(C)(2)Luyện miễn phí toàn bộ 120 câu hỏi — không cần đăng ký.
Câu hỏi liên quan cùng chủ đề
- A single-phase transformer has a 480-volt primary and a 120-volt secondary. If the secondary carries 100 amperes, what is the approximate primary current?
- What is the secondary full-load current of a 25 kVA single-phase transformer with a 240-volt secondary?
- A 480-volt panelboard is mounted on a wall with a grounded concrete wall directly behind the working space. What is the minimum depth of working space?
- What is the minimum width of working space in front of electrical equipment?
- The dedicated equipment space above a panelboard extends from the top of the equipment to what height?
- Which sequence correctly describes verifying that equipment is de-energized before beginning work?
Cập nhật gần nhất: · quy trình kiểm tra
Đội Ngũ Biên Tập PrepPass · Đối chiếu với Journeyman Electrician Licensing Exam (NEC-based) · Quy trình kiểm tra