Branch Circuits & FeedersCâu 16 / 120
Where must a multiwire branch circuit have a means to simultaneously disconnect all ungrounded conductors?
a.Only where the circuit supplies more than one device on a single yoke
b.At the first outlet box on the circuit
c.At each utilization equipment location
d.At the point where the branch circuit originates
Giải thích
Simultaneous disconnection of all ungrounded conductors is required at the point of origin, normally by handle ties or a multipole breaker in the panelboard, so no part of the shared neutral stays energized during service work. Disconnecting at the first outlet or at the equipment does not remove the hazard back at the panel, and the single-yoke rule is a separate requirement in 210.7.
Trích dẫn luật: 2023 NEC §210.4(B)Luyện miễn phí toàn bộ 120 câu hỏi — không cần đăng ký.
Câu hỏi liên quan cùng chủ đề
- A feeder supplies a 100-ampere continuous load. Using 75 degrees C terminations and copper THWN, what is the minimum feeder conductor size?
- Nine current-carrying 10 AWG THHN copper conductors share one raceway at a 30 degrees C ambient. What is the adjusted ampacity of each?
- A four-wire, three-phase, 208Y/120-volt feeder supplies electric-discharge lighting, and the major portion of the load is nonlinear. How many current-carrying conductors are counted for adjustment purposes?
- In a dwelling unit living room, no point measured horizontally along the floor line of any wall space may be more than what distance from a receptacle outlet?
- In a dwelling unit, 125-volt receptacles installed within what distance of the outside edge of a sink require GFCI protection?
- Arc-fault circuit-interrupter protection is required for 120-volt, single-phase, 15- and 20-ampere branch circuits supplying outlets in which dwelling unit areas?