Branch Circuits & FeedersCâu 25 / 120
Using the dwelling service and feeder conductor table, what is the minimum copper conductor size for a 200-ampere single-phase dwelling service?
a.1/0 AWG
b.3/0 AWG
c.4/0 AWG
d.2/0 AWG
Giải thích
For single-phase dwelling services and the main power feeder, conductors are permitted to be sized at 83 percent of the service rating, and the dwelling table lists 2/0 copper for a 200-ampere service. The 3/0 answer is what Table 310.16 alone would require without the dwelling allowance, and 1/0 is below what the dwelling table permits.
Trích dẫn luật: 2023 NEC §310.12Luyện miễn phí toàn bộ 120 câu hỏi — không cần đăng ký.
Câu hỏi liên quan cùng chủ đề
- What is the smallest conductor size generally permitted to be installed in parallel?
- The rule permitting the next higher standard overcurrent device rating above the conductor ampacity may be applied only where that device rating does not exceed what value?
- A 200-ampere feeder uses THHN copper conductors, but the equipment terminations are rated 75 degrees C. What is the minimum conductor size?
- What is the allowable ampacity of 4/0 AWG copper THWN in the 75 degrees C column?
- Twelve current-carrying 12 AWG THHN copper conductors run in one raceway through a 38 degrees C ambient. What is the adjusted ampacity of each conductor?
- A 5,000-watt, 240-volt single-phase electric heater operates continuously. What is the minimum standard branch-circuit overcurrent device rating?