Services, Grounding & BondingCâu 33 / 120
Where the grounding electrode conductor connects only to a driven ground rod, what is the largest size it is required to be?
a.2 AWG copper
b.4 AWG copper
c.6 AWG copper
d.1/0 AWG copper
Giải thích
A rod, pipe or plate electrode has a limited earth contact area, so the conductor to it is never required to be larger than 6 AWG copper regardless of what Table 250.66 would otherwise demand. The 4 AWG limit applies to a concrete-encased electrode, and larger sizes are not required for any rod connection.
Trích dẫn luật: 2023 NEC §250.66(A)Luyện miễn phí toàn bộ 120 câu hỏi — không cần đăng ký.
Câu hỏi liên quan cùng chủ đề
- A service uses 3/0 AWG copper ungrounded service-entrance conductors. What is the minimum size copper grounding electrode conductor?
- A service is supplied by two parallel sets of 250 kcmil copper conductors per phase. What is the minimum size copper grounding electrode conductor?
- Where the grounding electrode conductor connects only to a concrete-encased electrode, what is the largest size it is required to be?
- What is the minimum size copper equipment grounding conductor for a circuit protected at 60 amperes?
- A 200-ampere feeder requires what minimum size copper equipment grounding conductor?
- What is the minimum size copper equipment grounding conductor for a 400-ampere feeder?