Branch Circuits & FeedersCâu 5 / 120
A 120-volt circuit carries 20 amperes through 12 AWG copper (6,530 circular mils) to a load 100 feet away. Using K = 12.9, what is the approximate voltage drop?
a.10.5 volts
b.3.9 volts
c.5.2 volts
d.7.9 volts
Giải thích
For a single-phase circuit, VD = (2 x K x I x L) / CM = (2 x 12.9 x 20 x 100) / 6,530 = 51,600 / 6,530, or about 7.9 volts. The 3.9-volt answer forgets that current travels out and back, so it omits the factor of 2; 5.2 volts and 10.5 volts do not correspond to any correct combination of the formula terms.
Trích dẫn luật: 2023 NEC Chapter 9, Table 8Luyện miễn phí toàn bộ 120 câu hỏi — không cần đăng ký.
Câu hỏi liên quan cùng chủ đề
- For that same 24-ampere continuous load, what is the minimum size copper branch-circuit conductor, assuming 75 degrees C terminations and THWN insulation?
- Six current-carrying 12 AWG THHN copper conductors are installed in a single EMT run at a 30 degrees C ambient. What is the adjusted ampacity of each conductor before termination limits are applied?
- Four current-carrying 8 AWG THWN-2 copper conductors run in a raceway through a 48 degrees C ambient. What is the adjusted ampacity of each conductor?
- A 480-volt, three-phase feeder carries 40 amperes 250 feet using 6 AWG copper (26,240 circular mils). Using K = 12.9, what is the approximate voltage drop?
- A 120-volt branch circuit must carry 12 amperes 120 feet with voltage drop held to 3 percent. Using K = 12.9 for copper, what is the smallest conductor that meets the target?
- A feeder supplies 30 amperes of continuous load plus 50 amperes of noncontinuous load. What is the minimum standard overcurrent device rating?
Cập nhật gần nhất: · quy trình kiểm tra
Đội Ngũ Biên Tập PrepPass · Đối chiếu với Journeyman Electrician Licensing Exam (NEC-based) · Quy trình kiểm tra