What is the minimum trade size of EMT required for nine 12 AWG THHN conductors?
a.One-half inch
b.Three-quarter inch
c.One inch
d.One and one-quarter inch
Giải thích
Annex C, Table C1 shows that one-half inch EMT accepts nine 12 AWG THHN conductors, exactly meeting the requirement. Three-quarter inch EMT holds sixteen and one inch holds twenty-six, so both are larger than the minimum. Annex C may be used directly whenever all conductors are the same size and insulation type.
Trích dẫn luật: 2023 NEC Annex C, Table C1Luyện miễn phí toàn bộ 120 câu hỏi — không cần đăng ký.