Wiring Methods & MaterialsCâu 82 / 120
What is the minimum trade size of EMT required for twenty-four 12 AWG THHN conductors?
a.One inch
b.Three-quarter inch
c.One and one-quarter inch
d.One and one-half inch
Giải thích
Annex C, Table C1 shows one inch EMT accepts twenty-six 12 AWG THHN conductors, so twenty-four fit. Three-quarter inch holds only sixteen and is too small, while one and one-quarter inch holds far more than needed. Remember that twenty-four current-carrying conductors would also trigger a 45 percent ampacity adjustment.
Trích dẫn luật: 2023 NEC Annex C, Table C1Luyện miễn phí toàn bộ 120 câu hỏi — không cần đăng ký.
Câu hỏi liên quan cùng chủ đề
- An angle pull box has one 2-inch raceway and one 1-inch raceway entering the same wall, with conductors turning 90 degrees. What is the minimum distance from that wall to the opposite wall?
- How must liquidtight flexible metal conduit be secured on a normal run?
- How many 12 AWG conductors may be installed in a 4-11/16 inch by 2-1/8 inch square box with a volume of 42.0 cubic inches, assuming no clamps, devices or fittings?
- Direct-buried conductors emerging from grade must be protected by an approved enclosure or raceway from below grade to what height?
- What is the maximum fill percentage when exactly two conductors are installed in a raceway?
- Conductors installed in an underground raceway in a wet location must have which characteristic?
Cập nhật gần nhất: · quy trình kiểm tra
Đội Ngũ Biên Tập PrepPass · Đối chiếu với Journeyman Electrician Licensing Exam (NEC-based) · Quy trình kiểm tra