Gas PipingCâu 85 / 120
A house is served with natural gas having a heating value of about 1,000 Btu per cubic foot. The connected appliances are a 100,000 Btu/h furnace, a 40,000 Btu/h water heater and a 35,000 Btu/h clothes dryer. What total flow, in cubic feet per hour, must the piping downstream of the meter carry?
a.132 cfh
b.175 cfh
c.70 cfh
d.1,750 cfh
Giải thích
Add the loads: 100,000 + 40,000 + 35,000 = 175,000 Btu/h, then divide by the 1,000 Btu per cubic foot heating value to get 175 cfh. 132 cfh is what you get if the dryer is left out or a propane figure is mixed in; 70 cfh comes from dividing by 2,500, which is the propane heating value; 1,750 cfh comes from dividing by 100 instead of 1,000.
Trích dẫn luật: IFGC §402.4Luyện miễn phí toàn bộ 120 câu hỏi — không cần đăng ký.
Câu hỏi liên quan cùng chủ đề
- The same 175,000 Btu/h total connected load is served by LP-gas instead of natural gas. Using about 2,500 Btu per cubic foot for propane, what flow must the piping carry?
- A natural gas system runs from the meter through section A (12 ft), then section B (18 ft), then section C (35 ft) to the farthest appliance. Using the longest developed length method, which length is used to select the size of section A?
- Measured along the pipe, the most remote gas outlet in a building is 78 ft from the meter. Sizing tables are printed in 10 ft length increments. Which length row should be used?
- A residential natural gas system is supplied at about 7 in w.c. from the utility meter. Which allowable pressure drop is normally used with the standard low-pressure sizing tables for this system?
- A gas furnace sits in a basement mechanical room. Its manual shutoff valve is installed in an adjacent storage room 9 ft away, behind a closed door. Why does this installation fail inspection?
- On which of the following appliances does the IFGC NOT require a sediment trap ahead of the appliance control valve?