Gas PipingCâu 97 / 120
Which material is permitted for a buried gas service line running from an outdoor meter to a detached garage, but is prohibited for the piping inside the garage?
a.Polyethylene (PE) pipe
b.Schedule 40 black steel pipe
c.Corrugated stainless steel tubing
d.Type L copper tube
Giải thích
PE pipe is permitted only outside underground and must transition to an approved metallic material before it rises above grade or enters a building, and a tracer wire or other locating means must be buried with it. Black steel, CSST and copper (where the gas is not corrosive) are all approved for aboveground interior piping, so none of them are limited to underground use.
Trích dẫn luật: IFGC §403Luyện miễn phí toàn bộ 120 câu hỏi — không cần đăng ký.
Câu hỏi liên quan cùng chủ đề
- The same 3 psi test is applied to the piping with a mechanical gauge. What is the minimum time the pressure must be held without any loss?
- Which practice is correct when pressure testing a fuel gas piping system?
- A gas range is connected with a listed appliance connector that runs 4 ft from the shutoff valve to the range. Which statement about this installation is correct?
- A 250 gal propane tank is filled to 200 gal of usable propane. At about 91,500 Btu per gallon, roughly how many total Btu of energy are stored?
- A propane appliance with an input of 200,000 Btu/h runs continuously. Using about 91,500 Btu per gallon, about how long will 100 gal of propane last?
- A kitchen is served by a branch carrying only a 65,000 Btu/h range and a 40,000 Btu/h water heater, and that branch ends 15 ft from the meter, while the farthest outlet in the house is 90 ft from the meter. What load and what length are used to size this branch?
Cập nhật gần nhất: · quy trình kiểm tra
Đội Ngũ Biên Tập PrepPass · Đối chiếu với Journeyman Plumber Licensing Exam (UPC/IPC-based) · Quy trình kiểm tra