Gas PipingCâu 100 / 120
A kitchen is served by a branch carrying only a 65,000 Btu/h range and a 40,000 Btu/h water heater, and that branch ends 15 ft from the meter, while the farthest outlet in the house is 90 ft from the meter. What load and what length are used to size this branch?
a.105 cfh at 90 ft
b.65 cfh at 90 ft
c.175 cfh at 15 ft
d.105 cfh at 15 ft
Giải thích
The branch carries 65,000 + 40,000 = 105,000 Btu/h, which is 105 cfh of natural gas, and under the longest length method every section is sized from the 90 ft distance to the most remote outlet. Using 15 ft applies the section length instead of the developed length; 65 cfh drops the water heater; 175 cfh adds load that this branch does not actually carry.
Luyện miễn phí toàn bộ 120 câu hỏi — không cần đăng ký.
Câu hỏi liên quan cùng chủ đề
- A gas range is connected with a listed appliance connector that runs 4 ft from the shutoff valve to the range. Which statement about this installation is correct?
- Which material is permitted for a buried gas service line running from an outdoor meter to a detached garage, but is prohibited for the piping inside the garage?
- A 250 gal propane tank is filled to 200 gal of usable propane. At about 91,500 Btu per gallon, roughly how many total Btu of energy are stored?
- A propane appliance with an input of 200,000 Btu/h runs continuously. Using about 91,500 Btu per gallon, about how long will 100 gal of propane last?
- Gas piping passes through a concrete foundation wall below grade. What does the code require at that point?
- A line pressure regulator is installed on a 2 psi system serving a residence. Which requirement applies to that regulator?
Cập nhật gần nhất: · quy trình kiểm tra
Đội Ngũ Biên Tập PrepPass · Đối chiếu với Journeyman Plumber Licensing Exam (UPC/IPC-based) · Quy trình kiểm tra