A wet-niche underwater luminaire operating without GFCI protection is limited to a maximum of:
a.120 V
b.24 V
c.15 V
d.30 V
Giải thích
Underwater luminaires must be GFCI protected unless they operate at not more than the low-voltage contact limit of 15 V.
Trích dẫn luật: 2023 NEC 680.23(A)Luyện miễn phí toàn bộ 110 câu hỏi — không cần đăng ký.