Advanced WiringCâu 65 / 110
A single hermetic refrigerant motor-compressor has a rated-load current of 24 A. What minimum branch-circuit conductor ampacity is required?
a.30 A
b.24 A
c.36 A
d.28 A
Giải thích
Conductors to a single motor-compressor must be at least 125% of the rated-load or branch-circuit selection current: 24 x 1.25 = 30 A.
Trích dẫn luật: 2023 NEC 440.32Luyện miễn phí toàn bộ 110 câu hỏi — không cần đăng ký.
Câu hỏi liên quan cùng chủ đề
- A required convenience receptacle for a dwelling pool must be located not less than what distance from the inside pool wall?
- A wet-niche underwater luminaire operating without GFCI protection is limited to a maximum of:
- A motor disconnecting means must have an ampere rating of at least what percent of the motor full-load current?
- A hermetic compressor has a rated-load current of 24 A. What is the maximum branch-circuit short-circuit and ground-fault device at 175% (next standard size)?
- Which nameplate value on an air-conditioning unit is used to size the branch-circuit conductors?
- A Class 2 power-limited circuit at 30 V or less is limited to a maximum power of: