Code Admin & SafetyCâu 99 / 110
The dedicated equipment space above a panelboard extends how far above the equipment (or to a structural ceiling if lower)?
a.3 ft
b.4.5 ft
c.6 ft
d.7 ft
Giải thích
The dedicated electrical space extends from the equipment to 6 ft above it, or to a structural ceiling if lower, and must be kept clear of foreign systems.
Trích dẫn luật: 2023 NEC 110.26(E)(1)Luyện miễn phí toàn bộ 110 câu hỏi — không cần đăng ký.