PrepPass 团队 · 依据官方资料核对 the 2026 NEC (NFPA 70), checked section by section in November 2026, and PSI's Texas Department of Licensing and Regulation Electricians Candidate Information Bulletin (updated September 15, 2026) · 我们如何核对
免费试读 · 在线阅读第 1 章

Part 1. Your Code book is the tool

这是《Texas Journeyman Electrician Exam — Open-Book Study Guide (2026 NEC)》的第 1 章 —— 完整的一章,直接在此免费阅读;无需下载,无需邮箱。内容与电子书正文完全一致。读到结尾,完整指南只差一次点击。

The free part is Part 1: the Code book PSI lets into the room, how to mark it up before exam day, what moved in the 2026 edition, working the clock and the formula pages.

The exam is open book. The Code book answers every Code question on the exam, but only if you reach the right page in time. This part is about that: a book that is legal to bring, marked so your eye lands on the right line, and a way of working the clock.

1.1 A book PSI will let into the room

PSI's bulletin (updated September 15, 2026) sets these rules for the Code book you bring:

AllowedNot allowed
Any soft-bound edition of the NEC (questions follow the 2026 edition)Loose-leaf, spiral-bound or ring-bound copies
Highlighting, underlining and notes made before the exam sessionWriting, highlighting, underlining or marking the book during the session
Permanent index tabs made or supplied by the NEC book's publisherHomemade, DIY or other non-NEC tabs
A non-programmable, silent, battery calculator with no alphabet keyboard and no paper tapeAny added paper: loose, taped, stapled or stuck in
The NEC Handbook

PSI provides an electronic notepad. A candidate who arrives with a book that breaks these rules is offered three choices: test without the book, remove the non-compliant tabs, or forfeit the fee and test another day.

Two practical points follow. First, do all of your marking at home; the pen and highlighter stay outside. Second, check your tabs: if they did not come from the Code book's publisher, take them off before exam day.

1.2 Mark it up before exam day

Highlighting and notes are allowed as long as they are in the book before the session starts. Use that. A marked book turns a search into a glance.

A workable system:

  1. One colour for numbers you will be asked for (a distance, a percentage, an ampere rating). Highlight the number and the two or three words that say what it applies to.
  2. A second colour for the words that flip an answer: "not less than", "not more than", "continuous", "dwelling", "other than".
  3. Mark exceptions as exceptions. PSI says not to use an exception unless the question tells you to. Bracket each one in the margin so you do not read it as the main rule under time pressure.
  4. Write the next stop in the margin. Where a calculation sends you from one section to a table, write the table number beside the section. Chapter by chapter, this book gives you those chains.
  5. Write on the table pages which column to use. For ampacity questions the terminal temperature rating picks the column; note that beside the table heading.

Tabs

PSI's bulletin allows permanent index tabs manufactured or provided by the publisher of your Code book, and bars homemade, DIY and non-NEC tabs. A set from any other maker is not on the allowed list: do not put it on. A candidate who arrives with such tabs has to remove them, test without the book, or forfeit the fee and come back another day.

Putting a tab set on well takes about an hour:

  1. Check every tab against the 2026 contents first. A set printed for an earlier edition carries article numbers that have moved (see section 1.3).
  2. Start at the back of the book and work forward, so the tabs already placed never hide the page you are looking for.
  3. Put each tab on the right-hand page where its article or table begins, and step the tabs down the edge in rows so that no tab covers another.
  4. Press each tab down firmly. The bulletin's word for the tabs it allows is permanent, and it bars any added paper, loose or attached.
  5. If you have more tabs than patience, place these first: Article 100, Article 110, Article 120, Article 210, Article 215, Article 230, Article 240, Article 250, Article 300, Article 310, Article 314, Article 406, Article 430, Article 500, Article 501, Article 690, Chapter 9 tables. They are the articles this book sends you to most often.

Tabs get you to the article. Your highlighting gets you to the line. You need both.

The list below is where to start. These are the 40 places in the 2026 Code that this book's chapters and practice bank point to most often. That is a measure of this book, taken from its own pages; it does not predict what PSI will ask.

Open toWhat to mark there
Article 100Continuous load; Feeder; Class A GFCI
§110.26Working space width; Dedicated electrical space; Headroom
Table 110.26(A)(1)Working space depth; Depth by condition
Table 120.45Warehouse lighting demand; Lighting demand
§120.53Fastened-in-place appliances
Table 120.55Household ranges
§120.61Neutral load; Neutral reduction threshold; Neutral reduction amount
§210.11Small-appliance circuits; Laundry circuit; Bathroom circuit
§210.20Device for continuous load
§210.23Cord-and-plug limit; Fastened-in-place limit; Circuits over 50 amperes
§210.52Wall space; Countertop spacing; Countertop height; Garage receptacles
§215.4Feeder conductor ampacity; Feeder versus small service
§215.5Feeder overcurrent device
§230.24Clearance over driveways and streets; Clearance over roofs
§230.71Two to six disconnects; Maximum number
§230.79One-family dwelling minimum; Dwelling minimum rating
§240.21No rounding up on taps; 25-foot tap termination; Transformer tap length; High bay tap minimum
§250.52Concrete-encased electrode
§250.53Water pipe must be supplemented; Single rod resistance; Rod spacing
Table 250.66GEC sizing
Table 250.122Size by device rating; Grounding conductor size
§250.122Upsized conductors; Proportional increase; Upper limit
§300.6Bored holes in wood; Roof decking clearance
Table 300.7(A)Minimum cover
§310.15Apply both factors; Neutral as current-carrying
§314.16Device yoke
§314.27Fan support; Ceiling luminaire box; Wall luminaire on another box; Fan box marking
§314.28Straight pull; Angle pull
§406.9Damp-location cover; Wet-location cover; Tub and shower zone
§430.22Single motor conductor
§430.24Motor feeder conductor
§430.32Separate overload device; Will not start; Integral thermal protector
Table 430.52(C)(1)Squirrel-cage maximums; Wound-rotor breaker
§430.102Controller disconnect; Motor disconnect; One switch for both
§430.110General rating; Torque motor; Assumed locked-rotor current
§500.5Class I, Division 1; Ventilation-dependent room; Metal dust
§501.15Shared seal; Seal fill
§690.8Conductor ampacity; Parallel modules; Common-return conductor
§690.12Array boundary; Outside the boundary; Initiation device location
Chapter 9, Table 8Conductor circular-mil areas for voltage drop

1.3 What moved in the 2026 edition

If you trained on an earlier edition, or your notes and tabs came from one, these are the moves that matter most on this exam. Each was confirmed on the 2026 page.

If your old notes sayIn the 2026 Code look in
Article 220, load calculationsArticle 120
Table 300.5, burial coverTable 300.7(A)
215.2, feeder conductor rating and size215.4
215.3, feeder overcurrent protection215.5
"In Sight From" in Article 100110.29
450.3 and its tables, transformer overcurrent protection450.5 and Tables 450.5(A) and 450.5(B)

The load-calculation move is the big one: every section you knew as 220.xx is now in Article 120, and a 2023 tab set will send you to the wrong place.

1.4 Working the clock

The Knowledge portion gives you 59 items in 130 minutes, about 2.2 minutes each. The Calculations portion gives you 26 items in 110 minutes, about 4.2 minutes each. One question shows at a time, the minutes remaining show at the top of the screen, and PSI's bulletin says you can go back to any question and change your answer while time remains.

That makes a two-pass method possible:

  1. First pass: answer what you can find quickly. Read the question, pick out the key word, go to the article, answer. If you have not found the rule in about the average time per item, enter your best choice, note the question number on the electronic notepad and move on.
  2. Second pass: return to your noted questions with the time you saved. A long search on one item now costs you nothing else.
  3. Last five minutes: make sure nothing is blank.

Three reading habits prevent most wrong answers:

  • Find the condition before the number. "Continuous", "dwelling unit", "75 degree C terminals", "aluminum", "more than three current-carrying conductors": each of these changes the table, the column or the multiplier.
  • Main rule unless told otherwise. No exceptions and no optional calculation method unless the question names one.
  • Copper unless told otherwise.

And one for the calculation portion: write every step on the notepad in the order the chapter gives it. The wrong options are usually the result of skipping a step, so a number that matches an option is not proof that it is right.

1.5 Formula pages

The only reference PSI's bulletin lists for the exam room is your Code book, and it bars any added paper. Notes written in the book before the session are allowed, so the formulas you want at hand can be written on the pages where you will use them, at home, ahead of time.

Circuit formulas (not in the Code; know them cold)

To findFormula
Voltage, current, resistanceE = I x R; I = E / R; R = E / I
Power, single-phase or dcP = E x I; P = I x I x R; P = (E x E) / R
Power, three-phaseP = 1.732 x E x I x power factor
Current from volt-amperes, single-phaseI = VA / E
Current from volt-amperes, three-phaseI = VA / (1.732 x E)
Horsepower to watts1 hp = 746 W
Efficiencyoutput / input
Percent voltage drop(volts dropped / circuit voltage) x 100

Voltage drop and fault current

To findFormulaOpen to
Voltage drop, single-phaseVD = (2 x K x I x L) / circular mils. L is the one-way length in feet; this book's worked examples use K = 12.9 for copperChapter 9, Table 8 for the circular-mil area
Voltage drop, three-phaseVD = (1.732 x K x I x L) / circular milsChapter 9, Table 8
Smallest conductor for a voltage-drop limitcircular mils = (2 x K x I x L) / volts allowed, then the first size in the table with at least that areaChapter 9, Table 8
Transformer full-load currentVA / E single-phase; VA / (1.732 x E) three-phase
Available fault current at transformer terminals (estimate)full-load current / impedance as a decimal (2% is 0.02)

Code calculations: the rule, in our words, and where to read it

Each row is a reminder of a rule this book teaches. Read the Code text at the place named before you rely on it, and write the next stop in the margin there.

Load calculations

Step or ruleWhat to doOpen to
Dwelling floor areaMeasured from outside dimensions and excluding open porches.§120.5(C)
Dwelling lighting load2 VA per square foot, which also covers general-use receptacles.§120.41
Lighting trackIn other than dwelling units, 150 VA for each 2 ft or fraction of 2 ft.§120.46(B)
Small-appliance and laundry load1,500 VA for each required circuit.§120.52
Fastened-in-place appliancesFour or more on the same dwelling feeder or service may be taken at 75 percent.§120.53
Dryer loadUse 5,000 VA or the nameplate rating, whichever is larger.§120.54
Neutral loadThe maximum net calculated load between the neutral and any one ungrounded conductor.§120.61(A)
Neutral reduction thresholdFor general loads, only the unbalanced load above 200 amperes may be reduced; the range, oven, cooking-unit and dryer portion may be taken at 70 percent under 120.61(B)(1).§120.61(B)
Neutral reduction amountThe portion over 200 amperes is taken at 70 percent.§120.61(B)(2)
Optional method general loadsFirst 8 kVA at 100 percent and the rest at 40 percent.§120.82(B)

Continuous loads: branch circuits, feeders, services

Step or ruleWhat to doOpen to
Conductor for continuous loadBranch-circuit conductors must have an ampacity of at least 125 percent of the continuous load.§210.19(A)(1)
Device for continuous loadRate the overcurrent device at not less than 125 percent of the continuous load.§210.20(A)
Feeder conductor ampacityThe conductor must carry the noncontinuous load plus 125 percent of the continuous load.§215.4(A)(1)
Feeder versus small serviceA feeder carrying the full load of service conductors of 55 amperes or less may not have less ampacity than they do.§215.4(C)
Feeder overcurrent deviceRate the device for the noncontinuous load plus 125 percent of the continuous load, then go to the next standard size.§215.5
Service conductor ampacityAt least the noncontinuous load plus 125 percent of the continuous load.§230.42(A)(1)

Ampacity, adjustment and correction

Step or ruleWhat to doOpen to
Termination temperatureCircuits rated 100 amperes or less are based on the 60 degrees C column unless the equipment is listed and marked otherwise.§110.14(C)(1)
Termination temperatureWith 75 degree C terminations the final ampacity comes from the 75 degree C column, even for 90 degree C wire.§110.14(C)(1)(b)
400-ampere dwelling serviceThe dwelling table lists 400 kcmil copper.Table 310.12(A)
Adjustment factorsMore than three current-carrying conductors: 80 percent for 4 to 6, 70 percent for 7 to 9, 50 percent for 10 to 20.Table 310.15(C)(1)
Apply both factorsAmbient correction and conductor-count adjustment are multiplied together on the table ampacity.§310.15
Neutral as current-carryingCount the neutral of a 4-wire wye circuit when most of the load is nonlinear.§310.15(E)
Table ampacityRead the column that matches the insulation for derating and the termination rating for the final size.Table 310.16

Grounding and bonding sizes

Step or ruleWhat to doOpen to
GEC sizingSelected by the size of the ungrounded service conductors, with parallel sets added together.Table 250.66
Cap for rod, pipe or plateNever required to be larger than 6 AWG copper.§250.66(A)
Cap for concrete-encased electrodeNever required to be larger than 4 AWG copper.§250.66(B)
Bonding jumper tableMain and supply-side bonding jumpers are sized from the ungrounded conductors, and where parallel conductors total more than 1,100 kcmil copper the jumper is at least 12.5 percent of that total area.Table 250.102(C)(1)
Size by device ratingRead the copper column at the row for the overcurrent device ahead of the feeder.Table 250.122
Upsized conductorsIncrease the equipment grounding conductor in proportion to the circular-mil increase of the ungrounded conductors.§250.122(D)
Upper limitThe grounding conductor need not be larger than the circuit conductors.§250.122(A)

Box fill and raceway fill

Step or ruleWhat to doOpen to
Volume allowance per conductorEach conductor takes the volume for its own size: 2.00 cubic inches for 14 AWG, 2.25 for 12 AWG, 2.50 for 10 AWG.Table 314.16(B)(4)
Device yokeA yoke or strap counts as two allowances based on the largest conductor connected to the device.§314.16(B)(4)
Fill percentagesOne conductor may fill 53 percent of the raceway, two may fill 31 percent, and more than two may fill 40 percent.Chapter 9, Table 1
Short nippleA nipple 24 inches or shorter between enclosures may be filled to 60 percent.Chapter 9, Table 1, Note 4
Rounding the conductor countFor conductors all the same size, round up only when the decimal is 0.8 or larger.Chapter 9, Table 1 and Notes to Tables, Note 7
Conductor area for voltage dropCircular mil areas come from the conductor properties table, for example 10,380 for 10 AWG and 16,510 for 8 AWG.Chapter 9, Table 8

Motors and air-conditioning equipment

Step or ruleWhat to doOpen to
Table current for wire and protectionConductors and short-circuit and ground-fault protection are sized from the Code full-load current tables, not from the nameplate.§430.6(A)(1)
Single motor conductorAmpacity must be at least 125 percent of the table full-load current.§430.22
Duty-cycle conductorIntermittent duty with a 15-minute rated motor is sized at 85 percent of nameplate current.Table 430.22(E)
Motor feeder conductor125 percent of the highest-rated motor plus the sum of the other full-load currents.§430.24
Separate overload device125 percent of nameplate with a service factor of 1.15 or more or a rise of 40 degrees C or less, otherwise 115 percent.§430.32(A)(1)
Will not startThe overload may be raised to 140 percent for the better-rated motors and 130 percent for all others.§430.32(C)
Integral thermal protectorTrip current is limited to 170, 156 or 140 percent depending on the table full-load current.§430.32(A)(2)
Number of overload unitsThree for a three-phase motor, one for a single-phase two-wire motor.Table 430.37
Squirrel-cage maximums175 percent for dual-element fuses, 250 percent for inverse-time breakers, 300 percent for non-time-delay fuses.Table 430.52(C)(1)
Next size upIf the calculated value is not a standard rating, the next higher standard size may be used.§430.52(C)(1)
Motor feeder deviceNot more than the largest branch device plus the other full-load currents, rounded down to a standard size.§430.62(A)
Compressor protectionThe short-circuit and ground-fault device is sized at no more than 175 percent of rated-load current.§440.22(A)
Manufacturer's maximum valuesWhere the maximum protective device ratings on the manufacturer's overload relay table for use with a motor controller are lower than the 440.22(A) or (B) value, the device may not exceed those marked values.§440.22(C)
Compressor conductorsConductors to a single motor-compressor carry at least 125 percent of rated-load or branch-circuit selection current.§440.32

Transformers

Step or ruleWhat to doOpen to
Primary-only protectionWith primary current of 9 amperes or more, the primary device may be 125 percent of that current, or the next higher standard rating.Table 450.5(B)

Photovoltaic circuits

Step or ruleWhat to doOpen to
Conductor ampacityTake 125 percent of short-circuit current for maximum current, then 125 percent again for the conductor.§690.8
Parallel modulesSum the parallel short-circuit currents, then multiply by 125 percent.§690.8(A)(1)(a)(1)
Common-return conductorIts ampacity is at least the sum of the individual circuit overcurrent device ratings.§690.8(C)
你已读完免费章节

获取完整指南

刚才是全书 5 章中的第 1 章 —— 完整的一章,与正式版一字不差。其余各章以同样的深度讲透考试的每个部分,还附带练习题与答案解析 —— 一份可永久保存的干净 PDF 与 EPUB。

  • PSI's published content outline on one page: the scored items per content area for both portions (bulletin updated September 15, 2026)
  • A 20-question diagnostic, two questions from each of PSI's ten content areas, to tell you which areas to study first
  • Setting up your own 2026 NEC: the tabs and markings PSI allows, what moved in the 2026 edition, and a clock plan for each portion
  • A finder table for each of the ten content areas: from the kind of question to the section or table to open
  • Ten chapters in PSI's content areas, each ending with a short check, 40 questions in all
  • 29 timed find-it drills, each answered with the section to open first
  • Two full practice portions sized to PSI's scored items: 56 NEC Knowledge questions in 130 minutes and 24 Calculations questions in 110 minutes, every answer explained
  • A question-bank appendix: 275 more questions in PSI's ten content areas, with answers and explanations, for 444 practice questions in the book
  • Formula pages, a seven-day final plan and an A to Z index from key word to Code section
  • Reads alongside your own 2026 NEC: section and table numbers with explanations in our own words, no Code text
  • PDF (print it) + EPUB (phone / e-reader)

拥有整本书 — PDF + EPUB

练习题和计时模考永远免费。这本书是「学」的那一半:

  • 逐章系统讲解——每个考试章节按顺序讲透,不只是刷题
  • 可打印、贴标签——一本能划重点、做标记的纸质参考书
  • 离线可用——PDF 用来打印,EPUB 放进手机或阅读器
  • 全部在一个文件里——所有章节集中一处,可搜索、可打印

本书为英文版,下载的 PDF 与 EPUB 均为英文。

$14.99一次买断 · 永久下载 · 无订阅

14 天退款保证——不满意?发邮件即可全额退款,无需理由。 退款政策

本站提供免费样章——先读后买。一次付款解锁整本书,PDF + EPUB 永久保存。

两门都要考?有套装价

  • Texas Journeyman Electrician Exam — Open-Book Study Guide (2026 NEC)$14.99
  • Texas Journeyman Electrician — 2026 NEC Finder Sheet (2026)$9.99

两件一起买:$17.99 —— 比分开买省 $6.99

分开买 $24.98 · 立减 27% · 一次结账,两件都到手。

已经买过《Texas Journeyman Electrician (TDLR / PSI, 2026 NEC)》了?那就别买套装——套装里含这本,你会重复付费。单独购买《Texas Journeyman Electrician (TDLR / PSI, 2026 NEC)》只要 $14.99。 Texas Journeyman Electrician (TDLR / PSI, 2026 NEC) · 套装内容 →

一次买断 $14.99 · PDF + EPUB · 永久归你 · 查看完整目录。

免费试读 —— Texas Journeyman Electrician (TDLR / PSI, 2026 NEC) 学习指南中完整的一章。仅为教育性摘要,非专业或法律意见 —— 请始终以官方来源核实当前规定。最后更新:August 2026。