Certify cabling with the right instruments, commission systems, and turn over records, O&M data and training. CSLB weights this section at 17%. For worked examples, named traps and a full practice exam at CSLB's weights, see the PrepPass C-7 Low Voltage Systems study guide.
Testing
Match tester level to category; test fiber for loss and, where specified, with an OTDR.
Tester levels
IIe Cat 5e, III Cat 6, IIIe Cat 6A at 500 MHz.
UFC 3-580-01 (2024), Table 2-14Fiber acceptance
Connector 0.5 dB or less; splice 0.3 dB or less.
UFGS 27 10 00 (2025), para. 3.11.1.2OTDR distance
Time converts to distance with the operator-set group index.
NBSIR 87-3078Closeout
Test results, as-builts, records and owner training.
Package
Test results with as-built labeling records as one package.
UFGS 27 10 00 (2025), para. 3.11.1Failures
Corrected before turnover.
UFC 3-580-01 (2024), para. 2-6.5Commissioning
Required where more than passive equipment is provided.
UFC 3-580-01 (2024), para. 2-7