Chapter 3 of 712% of exam

Wire/Cable Installation and Termination

Install and support pathways, pull without damage, terminate with the right tools and keep every cable labeled. CSLB weights this section at 12%. For worked examples, named traps and a full practice exam at CSLB's weights, see the PrepPass C-7 Low Voltage Systems study guide.

Placement

Tension, bend radius and support rules protect the cable's performance.

Tension
25 pounds maximum on four-pair copper, monitored.
UFGS 27 10 00 (2025), para. 3.4.2
Bend radius
UTP 4 × diameter; fiber 20 × pulling, 10 × installed.
UFGS 27 10 00 (2025), para. 3.4.2
J-hooks
4 to 5 feet apart, 20 cables maximum, attached to structure.
UFGS 27 10 00 (2025), para. 3.3.4

Termination and labeling

IDC tools, minimal untwist, printed labels at both ends.

Untwist
No more than 1/2 inch at the termination.
UFGS 27 10 00 (2025), para. 3.4.2
Labels
Mechanically printed, To/From at both ends; handwritten labels unacceptable.
UFGS 27 10 00 (2025), para. 3.8
Shared boxes
Class 2 and 3 conductors stay out of power boxes and raceways without a barrier.
Cal. Code Regs. tit. 8 §2585.3