Browse all questions

Every question with its answer and explanation — study by topic or all at once.

Type III — Low-Pressure

40 questions
1. A technician is recovering R-11 from a low-pressure centrifugal chiller for a tear-down. To what evacuation level must the appliance be recovered?
a.25 mm Hg absolute
b.10 inches Hg vacuum
c.15 psig
d.4 inches Hg vacuum

Low-pressure appliances must be evacuated to 25 mm Hg absolute, a deep vacuum roughly equal to 29 inches of mercury vacuum. This level is the same whether the recovery equipment was made before or after November 15, 1993. The inches-of-mercury figures apply to high-pressure systems, not low-pressure chillers.

40 CFR §82.156
2. When pressurizing a low-pressure appliance to search for leaks, what is the maximum pressure a technician may apply?
a.5 psig
b.10 psig
c.15 psig
d.20 psig

A low-pressure appliance must never be pressurized above 10 psig. The shell is protected by a rupture disk that typically relieves at 15 psig, so staying under 10 psig keeps a safe margin below that disk. Higher pressures risk bursting the rupture disk and venting the charge.

40 CFR §82.156
3. The rupture disk on a low-pressure chiller is a safety device that is typically designed to relieve at what pressure?
a.10 psig
b.12 psig
c.15 psig
d.25 psig

The rupture disk on a low-pressure chiller is generally set to relieve at 15 psig, protecting the low-pressure shell from over-pressurization. This is exactly why leak-test pressure must stay at or below 10 psig. The disk must never be bypassed or blocked.

4. What is the primary purpose of a purge unit on a low-pressure centrifugal chiller?
a.To add refrigerant to the system
b.To lubricate the compressor bearings
c.To circulate chilled water
d.To remove non-condensable gases such as air

A purge unit removes non-condensable gases, mainly air and moisture, that leak into a chiller running under vacuum and collect at the top of the condenser. Removing them lowers head pressure and restores efficiency. A high-efficiency purge unit also recovers refrigerant vapor before venting the air.

5. Which of the following is a low-pressure refrigerant used in centrifugal chillers?
a.HCFC-123
b.HFC-410A
c.HCFC-22
d.HFC-404A

HCFC-123 is a classic low-pressure chiller refrigerant, along with CFC-11 and the newer HFO R-1233zd. R-410A, R-22, and R-404A are all high-pressure refrigerants that operate above atmospheric pressure and fall under Type II. Low-pressure refrigerants boil above about 50°F at atmospheric pressure.

40 CFR §82.152
6. Because a low-pressure chiller operates in a vacuum on the low side, what happens when it develops a leak?
a.Refrigerant sprays out rapidly
b.Air and moisture are drawn into the system
c.The system pressure rises sharply
d.Nothing changes until the charge is empty

Since the low side runs below atmospheric pressure, a leak pulls air and moisture inward rather than pushing refrigerant out. That incoming air becomes non-condensable gas the purge unit must remove, and the moisture can cause acid and corrosion. This inward leakage shapes nearly every Type III service procedure.

7. Water entering the refrigerant side of a low-pressure chiller through a leaking tube is dangerous mainly because it can:
a.Increase cooling capacity
b.Improve oil return
c.Cause acid formation and corrosion
d.Lower the refrigerant's boiling point

Water that leaks into the refrigerant side reacts to form acids, corrodes metal parts, can freeze and damage tubes, and contaminates the refrigerant. Because the chiller runs under vacuum, a tube leak lets cooling water be pulled inward. Any sign of water intrusion calls for investigation, not just resetting controls.

8. To speed up refrigerant recovery from a low-pressure chiller, a technician should:
a.Cool the chiller and warm the cylinder
b.Apply a torch to the chiller shell
c.Add nitrogen to raise pressure to 20 psig
d.Warm the refrigerant and keep the recovery cylinder cool

Recovery moves fastest when the refrigerant is warm and the recovery cylinder is cooler, so vapor naturally migrates toward the cold cylinder. Warm the chiller by circulating warm water or using built-in heaters, never a torch. Overpressurizing with nitrogen or applying open flame is unsafe.

9. Frequent operation of the purge unit on a low-pressure chiller is usually a sign that:
a.The machine has a leak drawing air in
b.The refrigerant charge is too high
c.The condenser water is too cold
d.The compressor is overcharged with oil

A rising purge rate means air is leaking into the vacuum side of the chiller, so the purge unit runs more often to remove it. The correct response is to find and repair the leak, not simply purge more. Modern high-efficiency purge units also track how much they run as a diagnostic.

10. A low-pressure refrigerant is defined as one with a boiling point at atmospheric pressure that is:
a.Below minus 50°F
b.Above about 50°F
c.Exactly 32°F
d.Between minus 50°F and 10°F

Low-pressure refrigerants boil above roughly 50°F at atmospheric pressure, so the appliance operates at or below atmospheric pressure. Refrigerants boiling between minus 50°F and 10°F are high-pressure, and those below minus 50°F are very-high-pressure. This boiling-point distinction sets which certification type applies.

11. Which gas is safe to use, along with a trace of refrigerant, to raise pressure in a low-pressure appliance for leak detection?
a.Oxygen
b.Compressed shop air
c.Dry nitrogen
d.Acetylene

Dry nitrogen is the correct pressurizing gas, sometimes with a small amount of refrigerant so an electronic detector can sense the leak. Oxygen or compressed air can combine with refrigerant oil and explode, and acetylene is a fuel gas. Even with nitrogen, never exceed 10 psig in a low-pressure appliance.

12. The 25 mm Hg absolute recovery requirement for low-pressure appliances applies to:
a.Only equipment made before 1993
b.Only equipment made after 1993
c.Only chillers over 200 pounds
d.All recovery equipment regardless of manufacture date

Unlike the high-pressure evacuation table, the low-pressure requirement of 25 mm Hg absolute is the same for recovery equipment made before or after November 15, 1993. There is no split based on equipment age or chiller size for low-pressure machines. This single deep-vacuum figure is a heavily tested Type III fact.

40 CFR §82.156
13. Approximately what inches-of-mercury vacuum reading corresponds to the 25 mm Hg absolute recovery level for low-pressure appliances?
a.About 29 inches Hg vacuum
b.About 15 inches Hg vacuum
c.About 10 inches Hg vacuum
d.About 4 inches Hg vacuum

25 mm Hg absolute is a deep vacuum equal to roughly 29 inches of mercury vacuum on a compound gauge, since atmospheric pressure is about 760 mm Hg or 30 inches Hg. This is far deeper than the 4 to 15 inches used for high-pressure systems. It reflects how completely a low-pressure chiller must be evacuated.

14. Non-condensable gases such as air that collect in a low-pressure chiller will:
a.Lower head pressure and save energy
b.Raise head pressure and reduce efficiency
c.Have no effect on operation
d.Increase the refrigerant charge

Non-condensable gases collect at the high point of the condenser and raise head pressure, which forces the compressor to work harder and cuts cooling efficiency. That is why the purge unit exists. Rising non-condensables also point to an air leak on the vacuum side that should be repaired.

15. Compared with older designs, a high-efficiency purge unit is desirable because it:
a.Purges air faster by venting more refrigerant
b.Eliminates the need for leak repair
c.Releases very little refrigerant per pound of air purged
d.Runs continuously to keep pressure high

A high-efficiency purge unit recovers refrigerant vapor before releasing the non-condensable air, so it loses far less refrigerant per pound of air purged than older units. It reduces both refrigerant emissions and operating cost. It does not replace the need to find and repair the air leak causing frequent purging.

16. A technician wants to warm the refrigerant in a low-pressure chiller to speed recovery. Which method is acceptable?
a.Applying a propane torch to the shell
b.Adding oxygen to raise pressure
c.Setting a space heater against the tubes
d.Circulating warm water through the chiller tubes

Circulating warm water through the chiller tubes gently raises refrigerant temperature and speeds recovery without risk. Using the machine's built-in heaters is also acceptable. An open flame such as a torch, or introducing oxygen, is dangerous and prohibited.

17. Low-pressure chillers most commonly use which type of compressor?
a.Centrifugal
b.Reciprocating hermetic
c.Rotary vane
d.Scroll

Low-pressure chillers typically use centrifugal compressors, which move large volumes of low-pressure refrigerant vapor to cool commercial buildings. Reciprocating, rotary, and scroll compressors are more common in higher-pressure and smaller systems. Recognizing the centrifugal chiller helps identify Type III equipment.

18. If a low-pressure chiller's high-pressure limit control trips during operation, the technician should first:
a.Reset it and keep running the machine
b.Investigate the cause before resetting
c.Bypass the control to finish the job
d.Raise the rupture-disk setting

A tripped limit control is a warning that should be investigated, since it may signal non-condensable buildup, water intrusion, or another fault. Simply resetting or bypassing a safety control hides the real problem and is unsafe. Never alter or bypass the rupture disk or limit devices.

19. When recovering from a low-pressure chiller with a large charge, the most efficient practice is to:
a.Recover vapor only
b.Recover with the purge unit running
c.Recover liquid first, then vapor
d.Recover only after adding nitrogen

Recovering liquid first moves the bulk of the charge quickly, then vapor recovery pulls the remaining refrigerant down to the required 25 mm Hg absolute. Recovering vapor alone is far slower on a large charge. The purge unit removes air but is not the recovery method.

20. The rupture disk on a low-pressure appliance should be:
a.Removed during recovery
b.Adjusted to a higher setting for leak testing
c.Replaced with a plug for service
d.Kept sound and never bypassed

The rupture disk is a critical safety device protecting the low-pressure shell and must be kept in good condition and never bypassed, plugged, or adjusted. Test pressure must stay below its typical 15 psig setting, which is why 10 psig is the leak-test limit. Tampering with it endangers the technician and the equipment.

21. A device that automatically maintains the correct refrigerant level between the condenser and evaporator of a low-pressure chiller is the:
a.Float valve
b.Rupture disk
c.Purge unit
d.Suction accumulator

A float valve meters refrigerant flow to maintain the proper level in a low-pressure chiller. The rupture disk is a pressure-relief safety device, the purge unit removes non-condensables, and an accumulator protects the compressor from liquid. Knowing the float's role helps in diagnosing chiller performance.

22. HCFC-123 requires good ventilation during service primarily because it:
a.Is highly flammable
b.Has a low exposure limit and can accumulate in low areas
c.Reacts violently with water
d.Freezes at room temperature

HCFC-123 has a relatively low allowable exposure limit, and like most refrigerants it is heavier than air and can accumulate near the floor in a machine room, displacing oxygen. Good ventilation and a refrigerant monitor protect the technician. It is not flammable, but exposure must still be controlled.

23. Before opening a low-pressure chiller to replace a failed tube bundle, the technician must:
a.Vent the charge slowly to the roof
b.Pressurize the shell to 20 psig
c.Recover the charge to 25 mm Hg absolute
d.Add nitrogen and leave the refrigerant in place

The refrigerant must be recovered to 25 mm Hg absolute before the machine is opened for major service such as a tube-bundle replacement. Venting is illegal, and pressurizing above 10 psig risks the rupture disk. Only after proper recovery may the low-pressure shell be opened.

40 CFR §82.156
24. R-1233zd is increasingly used in modern low-pressure chillers because it:
a.Is a CFC with high ODP
b.Operates at very high pressure
c.Requires no recovery
d.Is a low-GWP HFO replacement for HCFC-123

R-1233zd is a low-global-warming-potential HFO refrigerant used as a replacement for HCFC-123 in new low-pressure chillers. Like other low-pressure refrigerants it still runs in a vacuum and must be recovered to 25 mm Hg absolute. It has zero ozone depletion potential and a very low GWP.

25. Which statement about pressurizing a low-pressure appliance for leak detection is correct?
a.Keep pressure at or below 10 psig at all times
b.Pressure up to the rupture-disk setting is fine
c.Use compressed air for convenience
d.The higher the pressure, the safer the test

Leak-test pressure must stay at or below 10 psig to remain safely under the roughly 15 psig rupture disk. Approaching the disk setting or using compressed air is dangerous. Only dry nitrogen, sometimes with a trace of refrigerant, should be used.

26. A recovery cylinder used for a large low-pressure chiller should be:
a.A disposable one-trip cylinder
b.A refillable DOT-approved recovery cylinder
c.An open bucket for liquid
d.Any container that fits the refrigerant

Recovered refrigerant, including from low-pressure chillers, must be stored in a refillable DOT-approved recovery cylinder, never a disposable one-trip cylinder. The cylinder must be within its five-year test date and filled to no more than 80 percent. Using improper containers is illegal and dangerous.

27. During leak testing, some technicians raise the pressure in a low-pressure chiller just above atmospheric so that:
a.The rupture disk will vent
b.The refrigerant condenses faster
c.An electronic detector or bubble test can find the leak
d.The purge unit can be shut off permanently

Because the chiller normally runs in a vacuum, a leak pulls air in rather than out, so a detector cannot sense escaping refrigerant. Raising pressure slightly above atmospheric, staying under 10 psig, makes refrigerant flow outward at the leak so it can be found. The pressure must never approach the rupture-disk setting.

28. Low-loss fittings on recovery hoses are important on low-pressure work because they:
a.Increase system pressure
b.Speed up the compressor
c.Cool the refrigerant
d.Minimize refrigerant released when connecting and disconnecting

Low-loss fittings seal automatically to release as little refrigerant as possible each time hoses are connected or disconnected. This reduces emissions and conserves refrigerant on every job. They are good practice on all recovery work, not only low-pressure.

29. Which refrigerant is a CFC once widely used in low-pressure chillers and now available only as reclaimed stock?
a.CFC-11
b.HFC-134a
c.HFC-410A
d.HCFC-22

CFC-11 (R-11) was the classic low-pressure chiller refrigerant, but U.S. CFC production ended January 1, 1996, so it is now available only from recovered and reclaimed stock. R-134a, R-410A, and R-22 are not low-pressure CFC chiller refrigerants. This scarcity makes careful recovery of R-11 especially important.

30. A machine room housing a low-pressure chiller should have a refrigerant monitor and ventilation mainly to protect against:
a.Excess humidity damaging the walls
b.Oxygen displacement and refrigerant exposure
c.Static electricity
d.Frozen condenser water

Refrigerant vapor is heavier than air and can pool near the floor of a machine room, displacing oxygen and exposing workers. A refrigerant monitor and mechanical ventilation warn of a leak and clear the space. This is a standard safety requirement for chiller machine rooms.

31. The main reason a torch must never be used to warm a low-pressure chiller during recovery is that:
a.It wastes propane
b.It cools the refrigerant too fast
c.Open flame can decompose refrigerant into toxic gases and is a burn and pressure hazard
d.It has no effect on recovery speed

An open flame can break refrigerant down into toxic gases such as phosgene and hydrogen chloride, and localized heating can raise pressure dangerously and cause burns. Warm water or built-in heaters are the safe way to add heat. This is why torches are prohibited for warming the shell.

32. In a low-pressure chiller, the evaporator normally operates:
a.At very high positive pressure
b.At exactly atmospheric pressure
c.Above the condenser pressure
d.Below atmospheric pressure, in a vacuum

The evaporator of a low-pressure chiller runs below atmospheric pressure, that is, in a vacuum, because the refrigerant boils at a low temperature under low pressure. This vacuum is why leaks admit air and moisture. Understanding this is central to all Type III procedures.

33. A technician recovering R-123 reaches 25 mm Hg absolute but the reading rises back up after the recovery machine stops. This usually indicates:
a.Refrigerant is still boiling out of the oil or the machine has a leak
b.The recovery is complete and correct
c.The cylinder is empty
d.The rupture disk has failed

If the vacuum will not hold and pressure rises after the machine stops, refrigerant is still off-gassing from the oil, or air is leaking into the appliance or hoses. You must continue recovery or find the leak before considering the job done. A stable 25 mm Hg absolute is the target.

40 CFR §82.156
34. Which of the following is NOT a low-pressure appliance refrigerant?
a.CFC-11
b.HFC-404A
c.HCFC-123
d.R-1233zd

HFC-404A is a high-pressure blend used in commercial refrigeration, not a low-pressure chiller refrigerant. CFC-11, HCFC-123, and R-1233zd are all low-pressure refrigerants that run in a vacuum. Sorting refrigerants by pressure class is a common exam task.

35. Excessive water in a low-pressure chiller can freeze and rupture tubes because low-pressure refrigerants:
a.Boil at very high temperatures
b.Absorb water readily
c.Evaporate at low temperatures that can chill the water below freezing
d.Contain antifreeze additives

Because low-pressure refrigerants boil at low temperatures under vacuum, they can chill intruding water below its freezing point, and the expanding ice can rupture the chiller tubes. Water intrusion also causes acid and corrosion. This is one more reason to keep the machine tight and free of leaks.

36. When handling a large recovery cylinder of R-11 removed from a chiller, the technician must remember to:
a.Fill it completely to save space
b.Store it on its side near a heater
c.Leave the valve open to relieve pressure
d.Fill to no more than 80 percent and keep it cool

Even low-pressure refrigerant cylinders must never be filled above 80 percent by weight, leaving room for liquid expansion, and should be stored cool and upright below 125°F. Overfilling can lead to hydrostatic rupture as temperature rises. Always weigh the cylinder rather than guessing.

37. A high-efficiency purge unit on a chiller is often equipped with a purge-rate log because a rising rate:
a.Indicates a growing air or refrigerant leak needing repair
b.Means the chiller is running more efficiently
c.Shows the refrigerant is too cold
d.Confirms the rupture disk is working

Tracking the purge rate turns the purge unit into a leak-detection tool; a climbing rate signals that more air is entering the vacuum side, so the leak should be located and repaired. Ignoring it wastes refrigerant and energy. Modern purge controls log and alarm on excessive purging.

38. The deep 25 mm Hg absolute recovery requirement exists for low-pressure appliances because:
a.Their charge is very small
b.Their refrigerant boils near room temperature and must be pulled out thoroughly under deep vacuum
c.They contain no oil
d.They operate above atmospheric pressure

Low-pressure refrigerant boils near room temperature, so recovering it fully requires pulling the appliance down to a deep vacuum of 25 mm Hg absolute to draw out the remaining vapor. Shallow vacuums would leave significant refrigerant behind. The deep level ensures thorough recovery from these vacuum-operating machines.

40 CFR §82.156
39. Which practice is correct when leak testing a low-pressure chiller that is under a vacuum?
a.Draw a deeper vacuum to reveal leaks
b.Vent refrigerant to lower the pressure
c.Add nitrogen and refrigerant to raise pressure above atmospheric, staying under 10 psig
d.Pressurize with oxygen to 15 psig

To make a leak show outward, pressure must be raised above atmospheric, using nitrogen with a trace of refrigerant while staying at or below 10 psig. A deeper vacuum keeps leaks pulling air inward where a detector cannot sense them, venting is illegal, and oxygen is dangerous.

40. The main safety concern that sets the 10 psig pressurization limit on low-pressure appliances is:
a.Damaging the compressor windings
b.Overfilling the recovery cylinder
c.Freezing the condenser water
d.Bursting the rupture disk set near 15 psig

The 10 psig limit exists to keep test pressure safely below the rupture disk, which typically bursts near 15 psig to protect the low-pressure shell. Exceeding 10 psig risks rupturing the disk and releasing the charge. This is why nitrogen leak testing on these machines is done at low pressure.

Last reviewed: · editorial process

PrepPass Editorial Team · Verified against Clean Air Act §608 / 40 CFR Part 82 · How we review

What's on the EPA Section 608 Technician Certification Exam (Core, Type I, Type II, Type III / Universal)?

The EPA Section 608 Technician Certification Exam (Core, Type I, Type II, Type III / Universal) is administered by the Administered by EPA-approved certifying organizations (e.g., ESCO Institute, Mainstream Engineering, HVAC Excellence) under U.S. EPA oversight. Topic weights below come directly from the official exam blueprint — focus your study on the highest-weighted areas first.

Exam length
Core plus each Type has 25 multiple-choice questions; Universal requires all four sections (100 questions total)
Passing score
70%

Topic blueprint

  • 25%
    Core (Universal)
  • 15%
    Regulations & Safety
  • 15%
    Type I — Small Appliances
  • 15%
    Type II — High-Pressure
  • 15%
    Type III — Low-Pressure
  • 15%
    Recovery & Recycling

How hard is the exam?

Moderate. EPA 608 is taken as separate sections — Core plus Type I, II, and/or III — 25 questions each, closed-book and proctored, 70% (18 of 25) to pass each. Core is conceptual (ozone, regulations); the Type sections are hands-on refrigerant handling.

Recommended study hours
10-25 hours; Universal (all four sections) needs the most review.
First-attempt pass rate
Core and Type I pass easily; Type II is the most-failed section. Expect 1-2 attempts on the harder types.
Where to focus first
Core regulations (ozone, Clean Air Act, recovery) plus Type II high-pressure recovery/evacuation — the sections people retake most.

Frequently asked questions

How many EPA 608 practice questions are here?+

240 original practice questions across all four sections — Core, Type I (small appliances), Type II (high-pressure), and Type III (low-pressure) — plus recovery/recycling, in English and Español, with a 40 CFR Part 82 or Clean Air Act §608 citation on most answers.

Is this EPA 608 practice test free?+

Yes — completely free, no signup. Unlimited rounds, a full timed mock exam, and explanations included. The official EPA 608 certification exam (about $20-$100) is taken separately through an EPA-approved organization.

Are these real EPA 608 exam questions?+

No. All 240 questions are original prose written from the public-domain Clean Air Act Section 608 and 40 CFR Part 82. We never copy from any prep provider or the real exam.

How is the EPA 608 exam structured and what's the passing score?+

It has four sections — Core plus Type I, II, and III — 25 questions each, and you need 70% (about 18 of 25) to pass each. Passing Core plus all three types earns Universal certification. Core and the Type sections are proctored.

Does the EPA 608 certification expire?+

No — EPA Section 608 technician certification is valid for life and never expires.

What languages is the EPA 608 exam available in?+

Many EPA-approved organizations offer it in English and Spanish. PrepPass practice is available in English and Español.

Report