Type III — Low-PressureQuestion 193 of 240

A technician recovering R-123 reaches 25 mm Hg absolute but the reading rises back up after the recovery machine stops. This usually indicates:

a.The recovery is complete and correct
b.The cylinder is empty
c.Refrigerant still in the oil
d.The rupture disk has failed

Explanation

If the vacuum will not hold and pressure rises after the machine stops, refrigerant is still off-gassing from the oil, or air is leaking into the appliance or hoses. You must continue recovery or find the leak before considering the job done. A stable 25 mm Hg absolute is the target.

Law Reference: 40 CFR §82.156