Load & DesignPregunta 6 de 110
Using the sensible heat formula, how much sensible heat is removed when 1,200 CFM of air is cooled through a 20 degree F temperature drop?
a.12,960 BTU/hr
b.18,000 BTU/hr
c.25,920 BTU/hr
d.32,400 BTU/hr
Explicación
Sensible heat = 1.08 x 1,200 CFM x 20 F = 25,920 BTU/hr. This calculation lets a technician confirm the coil is delivering close to its rated capacity. A result far below expected suggests low airflow or an undercharged system.
Practica las 110 preguntas gratis — sin registro.
Preguntas relacionadas de este tema
- A common rule-of-thumb airflow value for a residential cooling system is approximately how many CFM per ton?
- A 4-ton air-conditioning system is designed at 400 CFM per ton. What total supply airflow is required?
- The sensible heat formula uses which constant when air volume is in CFM and temperature difference is in degrees F?
- What does ACCA Manual D provide guidance for?
- After a Manual J load is calculated, which ACCA procedure is used to select the specific equipment model?
- Oversizing a residential air conditioner most commonly leads to which problem?