Motors & EquipmentPregunta 102 de 120

A photovoltaic source circuit uses modules with a rated short-circuit current of 10 amperes. What minimum conductor ampacity is required before any temperature or conduit-fill adjustments?

a.12.5 amperes
b.15.6 amperes
c.10 amperes
d.20 amperes

Explicación

The maximum circuit current is 125 percent of the rated short-circuit current, or 10 x 1.25 = 12.5 A, and the conductor must then be sized at 125 percent of that value without adjustment factors: 12.5 x 1.25 = 15.6 A. The 12.5-ampere answer stops after only the first multiplier, and 10 amperes ignores both.

Referencia Legal: 2023 NEC §690.8