Branch Circuits & FeedersPregunta 26 de 120

What is the allowable ampacity of 4/0 AWG copper THWN in the 75 degrees C column?

a.195 amperes
b.205 amperes
c.260 amperes
d.230 amperes

Explicación

Table 310.16 lists 4/0 copper at 230 amperes in the 75 degrees C column. The 260-ampere figure is the 90 degrees C value and may be used only as a derating base, 195 amperes is the 60 degrees C value, and 205 amperes belongs to 3/0 copper at 90 degrees C rather than 4/0.

Referencia Legal: 2023 NEC Table 310.16

Practica las 120 preguntas gratis — sin registro.

Preguntas relacionadas de este tema

Última revisión: · proceso editorial

Equipo Editorial de PrepPass · Verificado con Journeyman Electrician Licensing Exam (NEC-based) · Cómo revisamos