Services, Grounding & BondingPregunta 37 de 120
What is the minimum size copper equipment grounding conductor for a 400-ampere feeder?
a.4 AWG
b.3 AWG
c.2 AWG
d.1 AWG
Explicación
Table 250.122 lists 3 AWG copper at 400 amperes. 4 AWG is the 300-ampere value, 2 AWG the 500-ampere value and 1 AWG the 600-ampere value, so all three are one row away from the correct entry.
Referencia Legal: 2023 NEC Table 250.122Practica las 120 preguntas gratis — sin registro.
Preguntas relacionadas de este tema
- Where the grounding electrode conductor connects only to a concrete-encased electrode, what is the largest size it is required to be?
- What is the minimum size copper equipment grounding conductor for a circuit protected at 60 amperes?
- A 200-ampere feeder requires what minimum size copper equipment grounding conductor?
- A 100-ampere feeder originally sized with 3 AWG copper (52,620 circular mils) is upsized to 1/0 AWG copper (105,600 circular mils) for voltage drop. What is the minimum equipment grounding conductor?
- A service is supplied by a single set of 500 kcmil copper ungrounded conductors. What is the minimum size copper main bonding jumper?
- A service uses two parallel sets of 750 kcmil copper per phase. Using the 12.5 percent rule, what is the minimum copper main bonding jumper?
Última revisión: · proceso editorial
Equipo Editorial de PrepPass · Verificado con Journeyman Electrician Licensing Exam (NEC-based) · Cómo revisamos