Branch Circuits & FeedersPregunta 6 de 120

A 480-volt, three-phase feeder carries 40 amperes 250 feet using 6 AWG copper (26,240 circular mils). Using K = 12.9, what is the approximate voltage drop?

a.14.8 volts
b.4.9 volts
c.8.5 volts
d.17.0 volts

Explicación

For three-phase, VD = (1.732 x K x I x L) / CM = (1.732 x 12.9 x 40 x 250) / 26,240, or about 8.5 volts, roughly 1.8 percent of 480 volts. The 17.0-volt answer uses the single-phase factor of 2 instead of 1.732, 4.9 volts halves the run length, and 14.8 volts does not follow from the given values.

Referencia Legal: 2023 NEC Chapter 9, Table 8