Motors & EquipmentPregunta 93 de 120
A continuous-duty motor over 1 horsepower is marked with a temperature rise of 40 degrees C but no service factor. What percentage of nameplate full-load current sets the maximum overload device?
a.140 percent
b.115 percent
c.125 percent
d.250 percent
Explicación
Motors with a marked temperature rise not over 40 degrees C, like those with a service factor of 1.15 or greater, are permitted overload protection at 125 percent of nameplate current. The 115 percent figure applies to all other motors, 140 percent is the allowance when the initial setting will not carry the load, and 250 percent is a short-circuit protection value.
Referencia Legal: 2023 NEC §430.32(A)(1)Practica las 120 preguntas gratis — sin registro.
Preguntas relacionadas de este tema
- A feeder supplies a 25-horsepower motor (34 amperes) and a 10-horsepower motor (14 amperes), both 460 volts three phase. What minimum conductor ampacity is required?
- For that same two-motor feeder, if the largest branch-circuit protective device is 90 amperes, what is the maximum feeder overcurrent device rating?
- When sizing motor branch-circuit conductors and short-circuit protection, which current value must be used?
- A continuous-duty motor over 1 horsepower has no marked service factor and no marked temperature rise. What is the maximum overload device rating as a percentage of nameplate full-load current?
- Where must a motor disconnecting means be located relative to the motor?
- An air conditioning condensing unit nameplate reads minimum circuit ampacity 24.6 and maximum overcurrent protective device 40. What overcurrent device must be installed?
Última revisión: · proceso editorial
Equipo Editorial de PrepPass · Verificado con Journeyman Electrician Licensing Exam (NEC-based) · Cómo revisamos