Motors & EquipmentPregunta 97 de 120

A hermetic refrigerant motor-compressor has a rated-load current of 20 amperes. What is the maximum branch-circuit short-circuit and ground-fault protective device at the standard 175 percent figure?

a.60 amperes
b.25 amperes
c.45 amperes
d.35 amperes

Explicación

Protection for a motor-compressor is sized at not more than 175 percent of the rated-load current: 20 x 1.75 = 35 A, which is a standard rating. Where that device still will not carry the starting current it may be increased, but never above 225 percent, which here would be 45 amperes. A 25-ampere device is below the calculated value and would nuisance trip on start.

Referencia Legal: 2023 NEC §440.22(A)

Practica las 120 preguntas gratis — sin registro.

Preguntas relacionadas de este tema

Última revisión: · proceso editorial

Equipo Editorial de PrepPass · Verificado con Journeyman Electrician Licensing Exam (NEC-based) · Cómo revisamos