Gas PipingPregunta 100 de 120

A kitchen is served by a branch carrying only a 65,000 Btu/h range and a 40,000 Btu/h water heater, and that branch ends 15 ft from the meter, while the farthest outlet in the house is 90 ft from the meter. What load and what length are used to size this branch?

a.105 cfh at 90 ft
b.65 cfh at 90 ft
c.175 cfh at 15 ft
d.105 cfh at 15 ft

Explicación

The branch carries 65,000 + 40,000 = 105,000 Btu/h, which is 105 cfh of natural gas, and under the longest length method every section is sized from the 90 ft distance to the most remote outlet. Using 15 ft applies the section length instead of the developed length; 65 cfh drops the water heater; 175 cfh adds load that this branch does not actually carry.