Water Supply & DistributionPregunta 45 de 120
An atmospheric vacuum breaker serves a fixture whose flood level rim is 34 in above the finished floor. What is the minimum height above the floor at which the vacuum breaker may be installed?
a.34 in
b.40 in
c.46 in
d.37 in
Explicación
An atmospheric vacuum breaker must be at least 6 in above the flood level rim, so 34 + 6 = 40 in above the floor. Installing it at 34 in puts it level with the rim with no clearance at all. The 37 in answer uses a 3 in clearance and 46 in uses the 12 in clearance required for a pressure vacuum breaker above its highest outlet.
Referencia Legal: IPC §608.13Practica las 120 preguntas gratis — sin registro.
Preguntas relacionadas de este tema
- A commercial kitchen is being piped with solenoid-operated quick-closing valves on the dishwasher and ice machine supplies. What does the code require on those branches?
- A potable water line supplies makeup water to a chemically treated boiler system and the connection is under continuous pressure. Which backflow prevention device is required?
- A fire sprinkler system with no antifreeze or chemical additives is connected to the potable water supply under continuous pressure. Which assembly is the appropriate minimum protection for this low hazard connection?
- A pressure vacuum breaker protects a lawn irrigation zone whose highest sprinkler head is 42 in above grade. What is the minimum height above grade for the vacuum breaker?
- Which condition makes a pressure vacuum breaker an unacceptable choice for a given cross-connection?
- Which copper tube designation has the heaviest wall thickness and is the type commonly required for an underground water service?
Última revisión: · proceso editorial
Equipo Editorial de PrepPass · Verificado con Journeyman Plumber Licensing Exam (UPC/IPC-based) · Cómo revisamos