Gas PipingPregunta 90 de 120

A gas furnace sits in a basement mechanical room. Its manual shutoff valve is installed in an adjacent storage room 9 ft away, behind a closed door. Why does this installation fail inspection?

a.Shutoff valves must be within 3 ft of the appliance
b.The shutoff must be within 6 ft of the appliance and in the same room as the appliance
c.Only the main valve at the meter is allowed to serve a furnace
d.The valve must be downstream of the appliance regulator

Explicación

Each appliance needs an accessible manual shutoff valve located in the same room as the appliance and within 6 ft of it, so a valve 9 ft away in another room is not acceptable. The 3 ft figure is a connector length limit, not a valve distance; a main valve at the meter does not satisfy the individual appliance shutoff; and the appliance shutoff belongs upstream of the appliance controls.

Referencia Legal: IFGC §409.5