CalculationsPregunta 17 de 110
A feeder supplies three motors with full-load currents of 34 A, 28 A, and 22 A. What minimum conductor ampacity is required for the feeder?
a.92.5 A
b.105 A
c.84 A
d.110 A
Explicación
Feeder ampacity = 125% of the largest motor FLC plus the sum of the others: (34 x 1.25) + 28 + 22 = 42.5 + 50 = 92.5 A.
Referencia Legal: 2023 NEC 430.24Practica las 110 preguntas gratis — sin registro.