For a 112.5-kVA, 208-V, three-phase transformer with 2% impedance, what is the approximate available fault current at the secondary terminals (infinite primary)?
a.6,250 A
b.20,000 A
c.10,000 A
d.15,617 A
Explicación
Secondary FLA = 112,500 / (1.732 x 208) = 312.3 A. Isc = FLA / %Z = 312.3 / 0.02 = 15,617 A.
Practica las 110 preguntas gratis — sin registro.
Preguntas relacionadas de este tema
- A 120-V branch circuit carries 16 A over a one-way run of 80 ft using #12 Cu (circular mils = 6,530, K = 12.9). What is the approximate voltage drop?
- Using the previous circuit (5.06-V drop on a 120-V circuit), what is the approximate percent voltage drop?
- A 208-V three-phase feeder carries 40 A over 150 ft using #6 Cu (CM = 26,240, K = 12.9). What is the approximate voltage drop?
- A 45-kVA, 208-V, three-phase transformer has 2% impedance. What is the approximate available fault current at its secondary (infinite primary)?
- Six current-carrying THHN conductors share one raceway. If the 90 C ampacity of #6 Cu is 75 A, what is the adjusted ampacity after the fill adjustment factor for 4-6 conductors?
- A #3 Cu THHN conductor has a 90 C ampacity of 110 A. In a 50 C ambient (correction factor 0.82), what is the corrected ampacity?