A panelboard is rated 225 A. What is the maximum rating of the overcurrent device that may protect it?
a.200 A
b.225 A
c.250 A
d.400 A
Explicación
Each panelboard must be protected by an overcurrent device rated no more than the panelboard rating, so 225 A is the maximum.
Referencia Legal: 2023 NEC 408.36Practica las 110 preguntas gratis — sin registro.
Preguntas relacionadas de este tema
- A feeder is protected by a 400-A overcurrent device. What is the minimum copper equipment grounding conductor?
- A service has 500-kcmil Cu ungrounded conductors per phase. What is the minimum copper grounded (neutral) service conductor for bonding purposes?
- Service phase conductors total 1,500 kcmil Cu per phase (over 1,100 kcmil). Using the 12.5% rule, what is the minimum copper main bonding jumper?
- Which of the following is the next standard overcurrent device rating above 95 A?
- Absent a specific exception, what is the maximum overcurrent protection for a #12 Cu conductor?
- Absent a specific exception, what is the maximum overcurrent protection for a #10 Cu conductor?