Advanced WiringPregunta 61 de 110
The equipotential bonding grid around a permanently installed pool must use a solid copper conductor no smaller than:
a.#8 AWG
b.#6 AWG
c.#10 AWG
d.#4 AWG
Explicación
Pool equipotential bonding must use an insulated, covered, or bare solid copper conductor not smaller than #8 AWG.
Referencia Legal: 2023 NEC 680.26(B)Practica las 110 preguntas gratis — sin registro.