Design & SizingPregunta 31 de 110

A drainage stack sizing table lists a 4 in stack at 500 DFU maximum and a 3 in stack at 48 DFU maximum for the total to a stack. A stack collects 240 DFU. What is the minimum stack size, and what secondary rule also applies?

a.3 in, and a cleanout is required
b.3 in, and no water closets allowed
c.4 in, and no size reduction downward
d.6 in, and a vent stack is required

Explicación

240 DFU exceeds the 48 DFU limit of a 3 in stack, so a 4 in stack is required, and a stack may never be reduced in size in the direction of flow as it descends. Downsizing a stack lower down would create a restriction that floods the branches above it. The stack must stay 4 in or larger to its base.

Referencia Legal: IPC §710.1

Practica las 110 preguntas gratis — sin registro.

Preguntas relacionadas de este tema

Última revisión: · proceso editorial

Equipo Editorial de PrepPass · Verificado con Master Plumber Licensing Exam (UPC/IPC-based) · Cómo revisamos