A horizontal fixture branch carries 30 DFU. The sizing table lists these branch capacities: 2 in = 6 DFU, 3 in = 20 DFU, 4 in = 160 DFU. Two of the fixtures are water closets. What is the minimum pipe size for the branch?
a.4 in
b.2 in
c.2-1/2 in
d.6 in
Explicación
The 30 DFU load exceeds the 20 DFU capacity of a 3 in branch, so the table already forces the next size, 4 in (160 DFU). The presence of water closets independently forbids anything smaller than 3 in, but here the load alone requires 4 in. Always pick the smallest size whose capacity equals or exceeds the load.
Referencia Legal: IPC §710.1Practica las 110 preguntas gratis — sin registro.
Preguntas relacionadas de este tema
- A copper water line has 90 ft of straight pipe. Fittings add an equivalent length of 3 ft each for four elbows and 8 ft for one gate valve. What is the developed (equivalent) length used for friction-loss calculations?
- Available pressure for friction is 30 psi and the total developed length of the water line is 150 ft. What is the maximum allowable uniform friction loss per 100 ft of pipe (the value used to enter a sizing chart)?
- A horizontal drainage branch carries the following drainage fixture units (DFU): 4 water closets at 4 DFU, 4 lavatories at 1 DFU, and 2 kitchen sinks at 2 DFU. What is the total DFU load carried by the branch?
- A 4 in building drain is run at the code minimum slope of 1/8 in per foot over a developed length of 96 ft. What is the total fall from the upstream end to the downstream end?
- A 2 in horizontal fixture drain must fall a total of 5 in over its run at the code minimum slope of 1/4 in per foot. How long is the run?
- A vent must be sized at not less than one-half the diameter of the drain it serves, and never smaller than 1-1/4 in. What is the minimum vent size for a 3 in drain?