Core TradesCâu 119 / 700
CALCULATION: A ceiling requires R-49 insulation. If a certain blown insulation provides R-3.5 per inch, what minimum installed thickness is needed?
a.About 10 inches
b.About 12 inches
c.About 14 inches
d.About 16 inches
Giải thích
Thickness = required R / R per inch = 49 / 3.5 = 14 inches. Answer 10 uses R-4.9 per inch; 12 and 16 use wrong per-inch values.
Trích dẫn luật: 2025 CA Energy Code (Title 24, Part 6)Luyện miễn phí toàn bộ 700 câu hỏi — không cần đăng ký.
Câu hỏi liên quan cùng chủ đề
- Behind exterior stucco or siding, a drainage gap or weep provision is often required so that:
- Fiberglass batt insulation is compressed and stuffed tightly around wiring and into a cavity that is too shallow. The effect on thermal performance is:
- In a mixed California climate, a vapor retarder placed on the WRONG side of the insulation can cause:
- A kickout (diverter) flashing is installed where a roof edge meets a vertical wall at the bottom of a roof-wall intersection. Omitting it commonly causes:
- Under normal ambient conditions, what is the MINIMUM period that standard structural concrete should be kept continuously moist to develop adequate strength and durability?
- What is the MINIMUM concrete cover required to protect reinforcing steel in concrete that is cast against and permanently exposed to earth?
Cập nhật gần nhất: · quy trình kiểm tra
Đội Ngũ Biên Tập PrepPass · Đối chiếu với California CSLB General Building (B) Trade Examination · Quy trình kiểm tra