A plan provides an attic access hatch of 20 in by 28 in for an attic that is over 30 square feet with more than 30 inches of headroom. What is the BEST correction?
a.Enlarge the opening to at least 22 in by 30 in
b.Reduce the opening because it is oversized
c.No opening is required for this attic
d.Only a scuttle in the garage is acceptable
Giải thích
An attic access opening is required where the attic area exceeds 30 square feet and headroom exceeds 30 inches, and the rough-framed opening must be at least 22 inches by 30 inches. A 20 by 28 opening is undersized and must be enlarged. Option b is backward. Option c ignores the trigger. Option d invents a restriction. Provide the minimum opening so equipment can pass and the attic is serviceable.
Trích dẫn luật: 2025 California Residential Code §R807.1Luyện miễn phí toàn bộ 700 câu hỏi — không cần đăng ký.
Câu hỏi liên quan cùng chủ đề
- A deck guard detail shows vertical balusters spaced so a 5-inch sphere can pass between them. What is the BEST correction?
- A stair section detail calls out a graspable handrail mounted 42 inches above the stair nosings. What is the BEST response during plan review?
- You are coordinating a whole-house remodel that adds a bedroom and a gas furnace. Which combination BEST reflects the required alarm coordination?
- A 1,800-square-foot crawl space uses standard (non-vapor-barrier) under-floor ventilation openings. Using the common 1-to-150 ratio, what is the MINIMUM net ventilation area required?
- During construction you find the architectural drawings show a beam at one size but the structural drawings show a larger size for the same beam. What is the BEST first action?
- Two days before bids are due, the architect issues a document that changes the window schedule for all bidders. What is this document BEST called?
Cập nhật gần nhất: · quy trình kiểm tra
Đội Ngũ Biên Tập PrepPass · Đối chiếu với California CSLB General Building (B) Trade Examination · Quy trình kiểm tra