When circuit conductors are run in parallel in multiple raceways, the equipment grounding conductor in each raceway must be:
a.Divided proportionally between raceways
b.Omitted in all but one raceway
c.One size smaller in each raceway
d.Sized in full, based on the circuit overcurrent device, in each raceway
Giải thích
Per 250.122(F), where conductors are run in parallel in separate raceways or cables, a full-size equipment grounding conductor sized per Table 250.122 (based on the circuit OCPD) must be installed in each raceway. It cannot be divided, reduced, or omitted, because each raceway must carry a complete fault path.
Trích dẫn luật: 2023 NEC §250.122Luyện miễn phí toàn bộ 521 câu hỏi — không cần đăng ký.
Câu hỏi liên quan cùng chủ đề
- Where the grounding electrode conductor connects to a made rod, pipe, or plate electrode, that portion of the conductor is not required to be larger than:
- For a feeder/service neutral, the portion of the maximum unbalanced load that exceeds 200 A may generally be calculated at:
- A 75 kVA, 208Y/120 V transformer has an impedance of 2%. Using the infinite-bus (worst-case) method, the approximate available fault current at the transformer secondary is about:
- A 208Y/120 V, 3-phase feeder supplies a balanced 50 kVA load. The approximate line current (and therefore the minimum conductor ampacity before continuous factors) is:
- For a 200 A service where the equipment and conductors are all rated for it, the conductor ampacity used for termination sizing is normally based on which temperature column?
- A panelboard must have a rating (busbar ampacity) not less than:
Cập nhật gần nhất: · quy trình kiểm tra
Đội Ngũ Biên Tập PrepPass · Đối chiếu với California CSLB C-10 Electrical Trade Examination · Quy trình kiểm tra